FireWarden 100-2/E — P/N 52778:A 11/04/2005 169
Appendix C: NFPA Standard-Specific Requirements
The NFW2-100 has been designed for use in commercial, industrial and institutional applications
and meets the requirements for service under the National Fire Protection Association (NFPA)
Standards outlined in this Appendix. The minimum system components required for compliance
with the appropriate NFPA standard are listed below:
NFW2-100 Control Panel
Contains the main control board, cabinet (backbox and door), main power supply transformer and
power supply.
Batteries
Refer to “Power Supply Calculations” on page 158, for Standby Power Requirements.
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to the control panel's Notification Appliance Circuits via a control module.
The following additional equipment is needed for compliance with the NFPA 72 standards listed
below:
NFPA 72 NATIONAL FIRE ALARM STANDARDS FOR:
NFPA 72 Central Station Service (Protected Premises Unit) or Remote Station Service
Onboard Digital Alarm Communicator Transmitter for connection to a compatible listed
Central Station DACR or Protected Premises Receiving Unit. This unit must be installed
as outlined in “Digital Alarm Communicator/Transmitter” on page 16.
OR
4XTM Transmitter Module for connection to the RS82 Remote Station Receiver. See
Figure C.2, “Remote Station Connection Using 4XTM Module,” on page 171, for
installation instructions for this unit.
NFPA 72 Auxiliary Fire Alarm System
4XTM Transmitter Module for connection to a compatible listed Local Energy Municipal Box.
This unit must be installed as illustrated in the section titled “4XTM Transmitter Module
Installation” on page 34 and as outlined in Figure C.1, “Municipal Box Connected to 4XTM
Transmitter Module,” on page 170.
NFPA 72 Proprietary Fire Alarm System
NFW2-100 Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure C.3,
“Proprietary Protective Signaling System,” on page 172, for installation instructions for this unit.
NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal
Box.
2. Cut JP3 on the NFW2-100 main circuit board to supervise placement of 4XTM module
and circuit.
3. Cut JP2 on the NFW2-100 main circuit board to enable FACP Supervisory relay.
4. Refer to “4XTM Transmitter Module Installation” on page 34 for detailed information.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER FireWarden-100-2 and is the answer not in the manual?

Honeywell NOTIFIER FireWarden-100-2 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER FireWarden-100-2
CategoryFire Alarms
LanguageEnglish

Related product manuals