FireWarden 100-2/E — P/N 52778:A 11/04/2005 77
Master Programming Level Programming
3.6.5 System Setup
System Setup allows the programmer to configure the following control panel features:
Trouble Reminder: This feature, when enabled, provides an audible reminder that an alarm
or trouble still exists on the FACP after the control panel has been silenced. The control
panel piezo sounder will pulse once every 15 seconds during an alarm and every two
minutes during a trouble condition, after the Alarm Silence or Acknowledge key is pressed.
The piezo will continue to sound at these rates until the alarm or trouble condition is cleared.
If the trouble condition is not cleared within 24 hours, the panel will reactivate the trouble
sounder and retransmit the trouble condition to the central station if connected.
Banner: This option allows the user to change the top two lines of the LCD display from the
factory default readout of HONEYWELL LIFE SAFETY to a user defined readout when the
control panel is in Normal condition.
Time-Date: This feature allows the programmer to set the time, display format (24 hr or 12
hr), date and daylight savings time feature into the FACP memory
Timers: This option allows the programmer to set the PAS (Positive Alarm Sequence) time
delay, Pre-Signal time delay and Waterflow time delay.
NACs: This feature allows the programmer to configure the control panel Notification
Appliance Circuits for a variety of options, such as circuit type, silenceable/nonsilenceable,
autosilence, coding, silence inhibit, zone assignment and enable/disable.
Relays: This option allows programming of two onboard relays for activation by various
control panel events, such as alarm, trouble, supervisory, etc.
Canadian Option: This option allows the automatic programming of ionization smoke
detector sensitivity thresholds to Canadian specifications.
Waterflow Silenceable: This option provides the ability to silence any output circuit
activated by a monitor module programmed as a waterflow type.
Pressing 2 for System Setup, while viewing Programming Screen #2, will cause the following
screens to be displayed:
PROGRAMMING
1=LOOP SETUP
2=SYSTEM SETUP
3=VERIFY LOOP
Programming Screen #2
SYSTEM SETUP
1=TROUBLE REM OFF
2=BANNER
3=TIME-DATE
System Setup Screen #1
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
SYSTEM SETUP
1=CANADIAN OPT. OFF
2=WATERFLOW SIL. NO
System Setup Screen #3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell NOTIFIER FireWarden-100-2 and is the answer not in the manual?

Honeywell NOTIFIER FireWarden-100-2 Specifications

General IconGeneral
BrandHoneywell
ModelNOTIFIER FireWarden-100-2
CategoryFire Alarms
LanguageEnglish

Related product manuals