120 FireWarden 100-2/E — P/N 52778:A  11/04/2005
Programming Maintenance Programming Level
The Zone No Output feature allows the programmer to view the zones which have not been 
programmed to at least one output device (not including general alarm Zone 00). The example in 
the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an 
addressable detector with an address of 001 on the loop but have not been programmed to any 
output devices.  Use the up and down arrow keys to view all the zones without output assignments.
3.7.4  Walktest 
To perform a walktest, press 1 while viewing Maintenance Screen #2.  The following screen will be 
displayed:
The operator can press 1 to perform a silent walktest or 2 to perform an audible walktest.  The 
display will read UNIT IN WALKTEST.  To end the Walktest, press the Esc (Escape) key.
Pressing 3 after the walktest has been completed, will allow the operator to view the results of the 
walktest.
3.7.5  System
To program the time and date into the control panel, press 2 while viewing Maintenance Screen #2.  
The following display will appear:
Pressing 1 while viewing the System Screen will cause the following screen to be displayed:
    PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
     WALKTEST
1=SILENT
2=AUDIBLE
3=VIEW RESULT
Walktest Screen   
     SYSTEMS
1=TIME/DATE
System Screen   
   TIME AND DATE
1=TIME  01:00 AM
2=DATE  01-01-2001
               12HR
Time and Date Screen