FireWarden 100-2/E — P/N 52778:A 11/04/2005 123
Maintenance Programming Level Programming
device connected to the control module can be used to indicate a PAS condition in the control
panel. Do not assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a
PAS condition.
Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause
the display to toggle between Pre-signal 98 On and Pre-signal 98 Off. When Zone 98 is
programmed On, a Pre-signal activation of any device will cause Zone 98 to activate. By assigning
Zone 98 to a control module in the Programming Zone Assignment Screen, an output device
connected to the control module can be used to indicate a Pre-signal condition in the control panel.
Do not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-
signal condition.
Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause
the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to “Two Stage
Operation” on page 87 for a description of this feature.