NO TE
Reinstall the heat re detector in a similar way as reinstalling the smoke detector, as
shown in Figure 5-7.
After the smoke detector or heat detector is reinstalled, the corresponding fault
indicator turns
o in about 3s.
Figure 5-6 Reference line for smoke detector installation
Figure 5-7 Reference line for heat detector installation
Step 15 Press Reset to reset the re alarm control panel.
Step 16 (Optional) Check whether the
re alarm signals are reported to the management
system.
Step 17 Reconnect cables to the electromagnetic valve.
FusionDC1000A Prefabricated All-in-One Data
Center
Commissioning Guide (IT Scenario) 5 System Commissioning
Issue 02 (2022-12-15) Copyright © Huawei Digital Power Technologies Co., Ltd. 71