Table 3-5 ETP48600-C5B1 technical specications
Item Technical Specications
Dimensions (W x D x H) 482.6 mm x 330 mm x 228 mm (including mounting
ears)
Weight ≤25 kg (excluding modules)
DC output surge
protection
Dierential mode: 10 kA (8/20 µs); common mode:
20 kA (8/20 µs)
AC input Three-phase input voltage range: 147–519 V AC
DC output Nominal voltage: –48 V DC
Output voltage range: –42 V DC to –58 V DC. The
default value is 53.5 V. The constant voltage 57 V
output is supported.
DC power distribution Battery circuit breakers: 6 x 125 A/1P
LLVD1 circuit breakers: 4 x 125 A/1P, 2 x 63 A/1P
LLVD2 circuit breakers: 2 x 125 A/1P, 5 x 63 A/1P
Expansion circuit breakers: 4 x 125 A/1P
Monitoring module SMU02C
Installation mode Installed in a 19-inch rack
Maintenance mode Maintained from the front
IP rating IP20
Figure 3-14 Intelligent circuit breaker (iCBD)
PowerCube 1000 (STC, Saudi Arabia, ICC800-A1-C2,
ESC800-A1)
Installation Guide 3 Component
Issue 02 (2021-09-28) Copyright © Huawei Technologies Co., Ltd. 32