LUNA2000-200KWH-2H1 Smart String ESS
User Manual
D CMU Commissioning
Copyright © Huawei Technologies Co., Ltd.
164
Main Menu
Second-Level Menu
Third-Level
Menu
Function
Restore factory settings.
Clears data.
Exports all configuration files.
Imports all configuration files.
Device Log
-
Exports device logs.
Device Mgmt.
Connect Device
Adds or removes a device.
Imports or exports configurations.
SmartModule
Removes the SmartModule.
Sets the authentication password.
Clear Alarm
Clears device alarms.
D.1.2 Maintenance Operations
D.1.2.1 Preparations and WebUI Login
Prerequisites
The operating system of Windows 7 or later is supported.
Browser: Chrome 52, Firefox 58, or Internet Explorer 9, or a later version is
recommended.
Procedure
Step 1 Connect the network cable between the network port of the PC and the WAN or LAN port of
the CMU.
Step 2 Set the IP address for the PC on the same network segment as the SmartLogger IP address.
Connected
Port
Item
CMU Default
Value
Example PC Setting
LAN port
IP address
192.168.8.10
192.168.8.11
Subnet mask
255.255.255.0
255.255.255.0
Default gateway
192.168.8.1
192.168.8.1
WAN port
IP address
192.168.0.10
192.168.0.11
Subnet mask
255.255.255.0
255.255.255.0
Default gateway
192.168.0.1
192.168.0.1