Item Description Setting
Single battery
capacity (Ah)
Species the
capacity of each
battery that is
connected in
series in a battery
string.
NOTICE
● If a third-party
UPS is
connected, set
this parameter
to the
maximum
value.
● If UPS from the
Company is
connected, set
Batt. charging
capacity
mismatch to
Disable on the
WebUI.
9999 (maximum value)
Batteries in a
battery string
Species the
number of
batteries in a
battery string.
8+8/8+0 scenario:
recommended
value 276, value
range 276–300
7+7/7+0 scenario:
recommended
value 252, value
range 240–270
6+6/6+0 scenario:
recommended
value 204, value
range 192–234
8+8/8+0 scenario:
recommended
value 46, value
range 46–50
7+7/7+0 scenario:
recommended
value 42, value
range 40–45
6+6/6+0 scenario:
recommended
value 34, value
range 32–39
Number of
battery strings
Species the
number of battery
strings connected
in parallel.
1
Cell oat voltage
(V/cell)
Species the
battery oat
charging voltage.
2.3
Cell equalized
volt. (V/cell)
Species the
battery equalized
charging voltage.
2.3
NOTICE
The UPS from the Company requires that
the equalized charging voltage be higher
than the oat charging voltage, so the
equalized charging voltage should be 0.01
V higher. For third-party UPSs, comply with
similar requirements if applicable.
SmartLi 3.0
User Manual (Short-Term Backup Power) 6 Power-On and Commissioning
Issue 10 (2024-01-31) Copyright © Huawei Digital Power Technologies Co., Ltd. 111