Figure 5-32 Cable connection for an EPO NO port
Figure 5-33 Cable connection for an EPO NC port
● If the NC state of EPO is used, remove the jumper between NC and 12V. When you turn
o the EPO switch, EPO is triggered.
● If the NO state of EPO is used, ensure that the jumper between NC and 12V is
connected. When you turn on the EPO switch, EPO is triggered.
5.7 Installing Battery Modules
Note the polarities when installing batteries. Do not connect the positive and
negative poles of a battery or battery string together. Otherwise, the battery may
be short-circuited.
The site must be equipped with qualied re suppression facilities, such as
halogenatedane, heptauoropropane, peruorohexanone, or carbon dioxide re
extinguishers and dry powder re extinguishers.
SmartLi 3.0
User Manual (Short-Term Backup Power) 5 Installation and Cable Connection
Issue 10 (2024-01-31) Copyright © Huawei Digital Power Technologies Co., Ltd. 84