Figure 6-21 Settings Wizard - System Param.
Table 6-7 System Param.
Item Description Default
Value
Value Range
Application scenario SmartLi connection scenario.
Currently, UPS scenarios are
supported.
UPS UPS, HVDC, EHU, SST
Battery cabinet
quantity
Species the number of battery
cabinets connected in parallel.
Currently, a maximum of 10 lithium
battery cabinets can be connected
in parallel.
1 1~10
Step 6 On the UPS LCD screen, choose System Info > Settings > Battery Settings and
check that Battery Type is set to Lithium battery.
Step 7 If the green indicator of one BCU blinks at super short intervals and the red
indicator is steady on, switch on the battery circuit breaker on the battery cabinet
where the indicator blinks at super short intervals. In this case, the green
indicators of all BCUs blink intermittently, and you cannot switch on the battery
circuit breakers on other battery cabinets or start the UPS in cold mode.
Step 8 Wait for about 15s. After the green indicators of other BCUs blink at super short
intervals and the red indicator is steady on, switch on the battery circuit breaker
on each battery cabinet where the green indicator on the BCU blinks at super
short intervals.
----End
6.2.2.2 Not Communicating with the UPS
Step 1 Ensure that no communications cable is connected between the SmartLi and the
UPS.
SmartLi 3.0
User Manual (Short-Term Backup Power) 6 Power-On and Commissioning
Issue 10 (2024-01-31) Copyright © Huawei Digital Power Technologies Co., Ltd. 122