EasyManua.ls Logo

Huawei SmartLi 3.0 - Component Technical Specifications

Huawei SmartLi 3.0
171 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Item Specications
Overcurrent protection Full-capacity cabinet (8+8 scenario):
Charge: level-1 protection: > 192 A; level-2 protection: > 300 A
Discharge: level-1 protection: > 780 A; level-2 protection: > 930 A
Full-capacity cabinet (7+7 scenario):
Charge: level-1 protection: > 192 A; level-2 protection: > 300 A
Discharge: level-1 protection: > 870 A; level-2 protection: > 930 A
Full-capacity cabinet (6+6 scenario):
Charge: level-1 protection: > 192 A; level-2 protection: > 300 A
Discharge: level-1 protection: > 870 A; level-2 protection: > 930 A
Half-capacity cabinet (8+0 scenario):
Charge: level-1 protection: > 96 A; level-2 protection: > 150 A
Discharge: level-1 protection: > 390 A; level-2 protection: > 465 A
Half-capacity cabinet (7+0 scenario):
Charge: level-1 protection: > 96 A; level-2 protection: > 150 A
Discharge: level-1 protection: > 435 A; level-2 protection: > 465 A
Half-capacity cabinet (6+0 scenario):
Charge: level-1 protection: > 96 A; level-2 protection: > 150 A
Discharge: level-1 protection: > 435 A; level-2 protection: > 465 A
EPO protection
Communication involved: You can trigger the EPO protection by
performing EPO on the UPS or over the specied dry contact.
Communication not involved: EPO can be triggered over the
specied dry contact.
3.2 Component Technical Specications
Table 3-7 BCU technical specications
Item
Specications
Dimensions (H x W x D) 130 mm x 442 mm x 550 mm
Weight < 36 kg
Table 3-8 Battery module technical specications
Item
Specications
Dimensions (H x W x D) 160 mm x 210 mm x 765 mm
Weight < 50 kg
SmartLi 3.0
User Manual (Short-Term Backup Power) 3 Technical Specications
Issue 10 (2024-01-31) Copyright © Huawei Digital Power Technologies Co., Ltd. 42