Step 6 After the green indicator of the BCU blinks at super short intervals and the red
indicator is steady on, switch on the battery circuit breaker on the battery cabinet.
----End
6.2.1.2 Not Communicating with the UPS
Step 1 Ensure that no communications cable is connected between the SmartLi and the
UPS.
Step 2 On the UPS LCD, choose System Info. > Settings > Battery Settings and set the
following parameters.
Item Description Setting
Battery type Species the type
of batteries
connected to the
UPS.
If the UPS does
not communicate
with the SmartLi,
the batteries are
managed as lead-
acid batteries by
default.
VRLA batt.
Single battery
voltage (V)
Species the
voltage of each
battery that is
connected in
series in a battery
string.
2 12
SmartLi 3.0
User Manual (Short-Term Backup Power) 6 Power-On and Commissioning