4.5 Battery Module Recharge
● Only trained and qualied personnel are allowed to recharge batteries. Wear
insulated gloves and use dedicated insulated tools during the operation.
● Observe onsite during recharge and handle any exceptions in a timely manner.
● If a battery experiences an abnormality such as bulging or smoking during
recharge, stop charging immediately and dispose of it.
● Do not use a third-party device to recharge a battery module. Otherwise, the
battery may be damaged.
Two methods are available for recharging a battery module. Select either one
based on site requirements.
Table 4-2 Battery module recharge methods
Recharge
Method
Application
Scenario
Recharge Restriction
Recharge in a
SmartLi cabinet
Recharging
multiple battery
modules at a time
● The number of battery modules to
be charged in the SmartLi cabinet
must meet the cabinet
conguration requirements. The
battery modules to be recharged at
the same time must be of the same
specications.
● Remove the BCU from the SmartLi
cabinet and install battery modules
in the cabinet. Before removing the
BCU, ensure that the SmartLi is
powered o. If you use this method,
ensure that services are not
aected.
Recharge with a
portable battery
charger/
discharger
Recharging one
battery module at
a time
-
Recharge in a SmartLi Cabinet
Do not use the customer's loads to recharge battery modules because completely
discharging the battery modules will cause the loads to power o.
SmartLi 3.0
User Manual (Short-Term Backup Power) 4 Transportation and Storage Requirements
Issue 10 (2024-01-31) Copyright © Huawei Digital Power Technologies Co., Ltd. 49