WebUI
● Exporting fault information
Choose Maintenance > Fault Information, set Encryption password for
export, click Export Fault Information, and specify a path to save the
exported data.
● Exporting e-labels
Choose Maintenance > E-Label, click Export All in the lower left corner, and
specify a path to save the exported data.
● Exporting historical data
Choose Query > Export Data and set Encryption password for export. In the
Data type drop-down list box, select All, Historical Alarm, Active Alarm,
Performance Data, Operation Log, or Security Log. Click Export historical
data and specify a path to save the exported data.
8.13 How Do I Switch the SmartLi from the Scenario
Involving Communication to the Scenario Not
Involving Communication?
Remove the communications cable between the SmartLi and the UPS, restore the
UI of the SmartLi to factory settings, and reset parameters by referring to the
section about the scenario not involving communication.
8.14 What Is the Heat Consumption of a Single SmartLi
Cabinet?
In the 8+8 scenario, the heat consumption of a single SmartLi cabinet is 2.65 kW.
In the 7+7 scenario, the heat consumption of a single SmartLi cabinet is 2.35 kW.
In the 6+6 scenario, the heat consumption of a single SmartLi cabinet is 2.05 kW.
You can select an appropriate air conditioner for the battery room based on the
data.
SmartLi 3.0
User Manual (Short-Term Backup Power) 8 FAQ
Issue 10 (2024-01-31) Copyright © Huawei Digital Power Technologies Co., Ltd. 154