Huawei SmartLi 3.0 - Page 132

Huawei SmartLi 3.0
171 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Step 2 On the UPS LCD, choose System Info. > Settings > Battery Settings and set the
following parameters.
Item Description Setting
Battery type Species the type
of batteries
connected to the
UPS.
If the UPS does
not communicate
with the SmartLi,
the batteries are
managed as lead-
acid batteries by
default.
VRLA batt.
Single battery
voltage (V)
Species the
voltage of each
battery that is
connected in
series in a battery
string.
2 12
Single battery
capacity (Ah)
Species the
capacity of each
battery that is
connected in
series in a battery
string.
NOTICE
If a third-party
UPS is
connected, set
this parameter
to the
maximum
value.
If UPS from the
Company is
connected, set
Batt. charging
capacity
mismatch to
Disable on the
WebUI.
9999 (maximum value)
SmartLi 3.0
User Manual (Short-Term Backup Power) 6 Power-On and Commissioning
Issue 10 (2024-01-31) Copyright © Huawei Digital Power Technologies Co., Ltd. 123