NO TICE
Set the preceding parameters and retain the default values for other
parameters.
The preceding parameters are described for UPS5000 series from the Company.
For third-party UPSs, set the parameters by referring to the preceding
description. If parameters are dierent, contact technical support.
If the preceding parameters are incorrectly set, the SmartLi cannot be charged
or discharged properly. In this case, contact technical support.
Step 3 Press and hold the POWER ON/OFF button on the BCU in the master cabinet for
more than 2s to power on the master cabinet. Then, power on slave cabinets one
by one in the same way.
NO TICE
The BCB o alarm (the red indicator is steady on) is displayed on the SmartLi
LCD. No action is required. After the battery circuit breaker is switched on, the
alarm will be automatically cleared.
The green indicator blinks intermittently. After 1 minute, the BCU starts. The
green indicator blinks at super short intervals and the red indicator is steady
on.
Step 4 Set the correct battery cabinet quantity on the SmartLi LCD.
Figure 6-22 Setting the correct battery cabinet quantity
Step 5 Obtain the startup password through the app. After the application is approved,
enter the startup password on the screen to complete battery cabinet
authorization.
SmartLi 3.0
User Manual (Short-Term Backup Power) 6 Power-On and Commissioning
Issue 10 (2024-01-31) Copyright © Huawei Digital Power Technologies Co., Ltd. 125