No. Check Item Acceptance Criteria Check Method and
Troubleshooting
Check Interval
4 Installation
position
There is no air exhaust
vent or refrigerant copper
pipe of the air conditioner
placed above the lithium
battery cabinet, and no
other water leakage risks
exist.
Check method: visual
inspection
Troubleshooting: Rectify
the fault based on the
acceptance criteria.
Monthly
5 Ambient
temperature
Actual temperature: ______
°C (Allowed temperature:
0°C to 40°C; recommended
temperature: 20°C to 25°C)
Check method: Measure
using a
hygrothermograph.
Troubleshooting: Check
that the air conditioner
runs properly.
Monthly
6 Ambient
humidity
Actual humidity: ______%
RH (5%–95% RH, non-
condensing)
Check method: Measure
using a
hygrothermograph.
Troubleshooting: Check
that the air conditioner
runs properly.
Monthly
Table 7-2 Product components
No.
Check Item Acceptance Criteria Check Method and
Troubleshooting
Check Interval
1 Cabinet
appearance
The cabinet is free from
dust (on air lters and
fans), rust, and
deformation.
Check method: visual
inspection
Troubleshooting: Rectify
the fault based on the
acceptance criteria.
Monthly
2 Battery
appearance
Batteries are free from
stains.
Battery wiring terminals
are intact.
Batteries are intact and
free of damage,
deformation, bulges,
and cracks.
Batteries have no acid
or electrolyte leakage.
(If electrolyte leakage
occurs, there will be a
pungent smell.)
Check method: visual
inspection
Troubleshooting:
Contact technical
support.
Monthly
SmartLi 3.0
User Manual (Short-Term Backup Power) 7 Maintenance