No. Check Item Acceptance Criteria Check Method and
Troubleshooting
Check Interval
4 Installation
position
There is no air exhaust
vent or refrigerant copper
pipe of the air conditioner
placed above the lithium
battery cabinet, and no
other water leakage risks
exist.
● Check method: visual
inspection
● Troubleshooting: Rectify
the fault based on the
acceptance criteria.
Monthly
5 Ambient
temperature
Actual temperature: ______
°C (Allowed temperature:
0°C to 40°C; recommended
temperature: 20°C to 25°C)
● Check method: Measure
using a
hygrothermograph.
● Troubleshooting: Check
that the air conditioner
runs properly.
Monthly
6 Ambient
humidity
Actual humidity: ______%
RH (5%–95% RH, non-
condensing)
● Check method: Measure
using a
hygrothermograph.
● Troubleshooting: Check
that the air conditioner
runs properly.
Monthly
Table 7-2 Product components
No.
Check Item Acceptance Criteria Check Method and
Troubleshooting
Check Interval
1 Cabinet
appearance
The cabinet is free from
dust (on air lters and
fans), rust, and
deformation.
● Check method: visual
inspection
● Troubleshooting: Rectify
the fault based on the
acceptance criteria.
Monthly
2 Battery
appearance
● Batteries are free from
stains.
● Battery wiring terminals
are intact.
● Batteries are intact and
free of damage,
deformation, bulges,
and cracks.
● Batteries have no acid
or electrolyte leakage.
(If electrolyte leakage
occurs, there will be a
pungent smell.)
● Check method: visual
inspection
● Troubleshooting:
Contact technical
support.
Monthly
SmartLi 3.0
User Manual (Short-Term Backup Power) 7 Maintenance
Issue 10 (2024-01-31) Copyright © Huawei Digital Power Technologies Co., Ltd. 138