Category Conguration Description
Battery
module
Mandatory The number of battery modules congured
in the SmartLi system must be a multiple
of 6, 7, or 8. The number of battery
modules congured in a single SmartLi can
be 8+8, 7+7, 6+6, 8+0, 7+0, or 6+0.
● Full-capacity cabinet: 8+8, 7+7, or 6+6
● Half-capacity cabinet: 8+0, 7+0, or 6+0
Battery bus
bar (BBB) box
Optional If battery copper bars are insucient, you
can install a BBB box to connect cables.
For details about the BBB box, see the
PDU8000-(0630, 1250, 2000) DCV8-
BGA001 BBB Box User Manual
.
Carbon
monoxide gas
sensor
Optional Detects the concentration of carbon
monoxide in the cabinet to determine
whether carbon monoxide is released from
battery modules because the vents are
opened due to thermal runaway.
4G module Optional The module exchanges data with related
equipment through wireless
communication. The model can be iIOT-
WAC0411 or iIOT-WAC0412.
Figure 2-3 Typical scenarios of conguring battery modules for the SmartLi
(1) Full-capacity cabinet (8+8
scenario)
(2) Half-capacity cabinet (8+0
scenario)
(3) Full-capacity cabinet (7+7
scenario)
SmartLi 3.0
User Manual (Short-Term Backup Power) 2 Product Overview
Issue 10 (2024-01-31) Copyright © Huawei Digital Power Technologies Co., Ltd. 26