Table 3-2 Environmental specications
Item Specications
Operating temperature 0–40°C
CAUTION
● When the operating temperature is beyond the range of 0°C to 40°C, the
power backup capability of the system may be unavailable or not reach
the rated value.
● When the operating temperature is below 0°C, the battery modules
switch o the charge and discharge circuits. As a result, the battery
modules cannot be charged or discharged. Start the air conditioner to
heat the battery modules to 3°C or above, and the charge and discharge
will be resumed.
Storage temperature 0–60°C
Relative humidity 5%–95% RH (non-condensing)
Altitude 0–4000 m (When the altitude ranges from 0 m to 1000 m, the
power is not derated. When the altitude exceeds 1000 m, the power
is derated as described in IEC 62040-3.)
Pollution degree Degree 2
Table 3-3 Safety
Item
Standard
CE EN 62619, EN IEC 62040-1
CB IEC 62619, IEC 62040-1
Table 3-4 EMC
Item
Standard
Certication standard EN IEC 62040-2
Conducted emission (CE) EN IEC 62040-2
Radiated emission (RE) EN 300386, Class A
Electrostatic discharge
(ESD) immunity
IEC 61000-4-2
Conducted susceptibility
(CS)
EN IEC 62040-2
EN/IEC 61000-4-6
Radiated susceptibility (RS) EN IEC 62040-2
EN/IEC 61000-4-3
SmartLi 3.0
User Manual (Short-Term Backup Power) 3 Technical Specications