Item 8+8
Scenario
7+7
Scenario
6+6
Scenario
8+0
Scenario
7+0
Scenario
6+0
Scenario
Backup
time
11.4 min 10 min 10 min 11.4 min 10 min 10 min
Discharge
capability
(Operating
temperature of
cells: 0–40°C)
Maximum
load
power
supported
by a single
cabinet
245 kW 215 kW 185 kW 115 kW 100 kW 85 kW
Backup
time
15 min 15 min 15 min 15 min 15 min 15 min
Maximum
load
power
supported
by a single
cabinet
285 kW 250 kW 215 kW 143 kW 125 kW 108 kW
Backup
time
10 min 10 min 10 min 10 min 10 min 10 min
Rated charge current 76.5 A/0.5C 38.3 A/0.5C
Discharge cut-o voltage The voltage per cell ranges from 2.5 V to 2.8 V. The default voltage
is 2.7 V when the temperature is greater than or equal to 25°C and
2.5 V when the temperature is less than 25°C.
Rated discharge current 630 A 315 A
Maximum number of UPS
modules supported
6 (UPS5000-H 100 kVA
modules)
12 (UPS5000-E 50 kVA
modules)
12 (UPS5000-E 30 kVA
modules)
8 (208 V UPS5000-E 20 kVA
modules)
NOTE
When the UPS5000-E-120K-FM,
UPS5000-E-180K-HABBS, UPS5000-
E-60K-HABBS/HASBS, UPS5000-
E-125K-HABBS/HASBS-01, or
UPS5000-E-160K-F160 is connected
and battery strings are not shared,
the number of UPS modules is not
limited.
3 (UPS5000-H 100 kVA
modules)
6 (UPS5000-E 50 kVA modules)
7 (UPS5000-E 30 kVA modules)
8 (208 V UPS5000-E 20 kVA
modules)
NOTE
When the UPS5000-E-120K-FM,
UPS5000-E-180K-HABBS, UPS5000-
E-60K-HABBS/HASBS, UPS5000-
E-125K-HABBS/HASBS-01, or
UPS5000-E-160K-F160 is connected
and battery strings are not shared,
the number of UPS modules is not
limited.
Number of cabinets
connected in parallel
10
Number of battery modules 16 14 12 8 7 6