Item Specications
30 kVA 60 kVA 90 kVA 120 kVA
Recommende
d cross-
sectional area
(mm
2
)
L1 4 x 10 4 x 35 4 x 70 4 x 95
L2
L3
N
Bypass
input
Bypass input current (A) 45 91 136 182
Recommende
d cross-
sectional area
(mm
2
)
L1 4 x 10 4 x 25 4 x 50 4 x 70
L2
L3
N
Output Output current (A) 45 91 136 182
Recommende
d cross-
sectional area
(mm
2
)
U 4 x 10 4 x 25 4 x 50 4 x 70
V
W
N
(When
the UPS
connect
s to a
non-
linear
load,
increase
the
cross-
section
al
area.)
Battery
input
(lead-
acid
battery)
Nominal discharge
current (A)
66 132 197 263
Maximum discharge
current (A)
79 158 236 315
Recommende
d cross-
sectional area
(mm
2
)
+ 3 x 16 3 x 50 3 x 70 3 x 120
N
-
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual 3 Installation
Issue 03 (2022-01-30) Copyright © Huawei Technologies Co., Ltd. 49