Item Specications
Rated voltage 380 V AC/400 V AC/415 V AC (line voltage)
Voltage range 0–30°C: not derated at 323–485 V AC, derated from 100%
load to 45% load at 323–191 V AC, and derated from 45%
load to 35% load at 191–138 V AC
30–40°C: not derated at 342–485 V AC, derated from 100%
load to 45% load at 342–191 V AC, and derated from 45%
load to 35% load at 191–138 V AC
Rated frequency 50 Hz/60 Hz
Frequency range 40–70 Hz
Power factor > 0.99 (full load); > 0.98 (half load)
Harmonic
current
THDi < 9% (30% linear load), THDi < 6% (50% linear
load), THDi < 3% (100% linear load)
THDi < 11% (30% non-linear load), THDi < 8% (50% non-
linear load), THDi < 5% (100% non-linear load)
NOTE
1. The preceding
specications are met when the mains input
and bypass input share a power source.
2. The input THDu is less than 2%.
Table 10-6 Bypass input electrical specications
Item
Specications
Power system Three-phase four-wire + PE
Rated voltage 380 V AC/400 V AC/415 V AC (line voltage)
Rated
frequency
50 Hz/60 Hz
Frequency
range
50 Hz/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6 Hz,
±2 Hz by default)
Input mode The mains input and bypass input share a power source (by
default) or use dierent power sources.
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 10 Technical Specications
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 100