Table 10-7 Battery electrical specications
Item Specications
Battery voltage
(lead-acid
battery)
360–600 V DC
12 V battery, 30–50 batteries, 0 by default; 40–50 batteries
without derating, 38–39 batteries with output power derated
to 0.9, 34–37 batteries with output power derated to 0.8, or
30–33 batteries with output power derated to 0.7
2 V battery, 180–300 batteries, 0 by default; 240–300 batteries
without derating, 228–239 batteries with output power
derated to 0.9, 204–227 batteries with output power derated
to 0.8, or 180–203 batteries with output power derated to 0.7
NOTE
The number of batteries is 0 by default and needs to be set based on
site requirements. Batteries have no neutral wire, and an odd number
of batteries are supported.
Battery cold
start
If a mains outage occurs, batteries can start the UPS to supply
power to loads.
Charger output
power
Under rated conditions, the maximum charge power is 15% of
power of a single module, and the charge current is limited to
30 A.
Battery string
sharing (lead-
acid battery)
Supported in a parallel system
Charging
voltage (lead-
acid battery)
Equalized charging voltage: 2.3–2.4 V/cell; default voltage:
2.35 V/cell
Float charging voltage: 2.23–2.3 V/cell; default voltage:
2.25 V/cell
Battery type VRLA
SmartLi
NO TICE
The UPS supports the SmartLi. For details about the parameters, see the
SmartLi
User Manual
.
Table 10-8 Output electrical specications
Item
400 kVA 500 kVA 600 kVA
Power
system
Three-phase four-wire + PE
Voltage 380 V AC/400 V AC/415 V AC (line voltage)
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 10 Technical Specications
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 101