Item 400 kVA 500 kVA 600 kVA
Frequency In normal mode, the frequency is synchronous with the
bypass input frequency.
In battery mode, the frequency is 50 Hz/60 Hz with a
tolerance of ±0.05%.
Voltage
distortion
Linear load THD < 1% (50–100% load balancing)
Non-linear load THD < 3% (50–100% load balancing)
Power factor 1
Transfer
time
(normal)
Uninterruptible transfer: 0 ms
Interruptible transfer: < 5 ms
Output
voltage
imbalance
100% unbalanced load voltage imbalance: ±1%
Phase imbalance: 120±1° (balanced load), 120±2° (unbalanced
load)
Overload
capability
Inverter overload capability:
105% < load ≤ 110%: transfers to bypass mode after 60 min
or longer (ambient temperature ≤ 30°C)
100% < load ≤ 110%: transfers to bypass mode after 60 min
or longer (ambient temperature > 30°C)
110% < load ≤ 125%: transfers to bypass mode after 10
minutes or longer (10±0.1 minutes)
125% < load ≤ 150%: transfers to bypass mode after 1 minute
or longer
Load > 150% or a short circuit occurs: transfers to bypass
mode after 200 ms or longer
Bypass overload
capability:
At 40°C:
110% load: 60
minutes
125% load: 10
minutes
150% load: 1
minute
Load > 150%: 100
ms
Bypass overload
capability:
At 30°C, load
≤ 135%: runs
for a long
time
At 40°C, load
≤ 125%: runs
for a long
time
Load >
1000%: 100
ms
Bypass overload
capability:
At 25°C, load ≤
125%: runs for a
long time
Load > 1000%:
100 ms
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 10 Technical Specications
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 102