Serial Communication Programmer Reference Guide
30 810400 Reference Guide Powermax65/85/105 SYNC
Response from plasma power supply:
:0110308000033C<CR><LF>
Refer also to Exit remote control mode on page 40.
Remote control mode indicator on the plasma power supply
When the Powermax65/85/105 SYNC enters
remote control mode, an indicator shows on the
LCD display.
The front panel controls are disabled when the
Powermax65/85/105 SYNC is in remote control
mode. Fault codes and fault icons still show, and
you can still go to the menu screens to see
information about the plasma power supply,
torch, and cartridge.
Refer also to Exit remote control mode on page 40.
Do a check for an active fault
Active faults must be resolved before cutting can start. To do a check for an active fault, the CNC
reads the value in the following register:
0x301A (active fault code)
If there is no active fault, the CNC can start cutting.
0x301A (active fault code)
Value Description
: Start of message
01 Plasma power supply node address (confirmed)
10 Write Multiple Registers (confirmed)
3080 First register address (confirmed)
0003 Quantity of registers to write (confirmed)
3C LRC
<CR><LF> End
Description: Reads the hexadecimal value of the fault code for a fault that is currently active on
the plasma power supply. If there is no active fault, this reads a value of 0x0000
(0-00-0).
Refer to Fault code list on page 32 for the complete list of possible fault codes.
Encoding or scaling: 10-bit effective unsigned binary number from the LSB of a 16-bit binary number
Unit: N/A
Function (hex): 04 (Read Registers)