84 MX3630-01 Rev. J SlideDriver/SlideDriver 50VF Series © 2019 www.hysecurity.com
Sequenced Gate: Configuration #2
Vehicle Loop Layout
Drawings not to scale.
*NOTICE
For sequenced gates to operate properly, all vehicle detectors must be wired to
the Trafc Control Gate.
If a communication failure occurs, an ALERT 22 (AL22) appears and the buzzer sounds.
The Trafc Control Gate maintains functionality while the Security Gate defaults to
open until communication is restored (or the Security Gate is manually closed).
PEDESTRIAN GATE & WALKWAY
SECURITY SLIDE GATE
A
B
D
E
D
C
C
F
D
Uni- or Bi-directional Trafc Control
Vehicles must pass from one loop to the
next without loss of detection.
Dimension “A” = 6 to 16 ft minimum to 16 ft
maximum (183 to 488 cm)
Dimension “B” = 6 to 8 ft minimum to 4 ft
maximum (91 to 122 cm)
Dimension “C” = 3 ft minimum to 4 ft
maximum. Distance from edge of Reset Loop
to C/L of the Security Gate is 3 to 4 ft (91 to
122 cm).
Dimension “D” = 6 ft (183 cm)
Dimension “E” = 4 ft mininum to 8 ft
maximum. Reset Loop can be offset from C/L
gate 1 to 5 ft (31 to 152 cm).
Dimension “F” = 10 to 15 ft (3 to 3.6 m)
INSIDE
OBSTRUCTION
LOOP
IOLD for Trafc Control Gate or
Free Exit for both operators.
If loop used as Free Exit,
you must have an OOLD loop.
OUTSIDE
OBSTRUCTION
LOOP
(OOLD for both opreators)
To sequence the gates, set the
Installer Menu item SG to “2” in
both gate operators.*
Operator & Loops**
As trafc control and security
gates are separated farther apart,
Reset Loop moves toward center.
StrongArm Crash
concrete foundation
shown 6 x 6 ft
(183 x 183 cm)
RESET LOOP
Loop can be offset from C/L
of gate 1 to 5 ft (31 to 152 cm).
IOLD for Security Gate
TRAFFIC CONTROL GATE
Optional access control
devices (card reader, etc.).
Align along 6 ft edge of
the Outside Obstruction
Loop.