System Service Clearances
The amount of space needed by the units during service is indicated by the dotted line
in the following figure.
For multiple racks placed side by side, the left and right clearances apply only to the
leftmost and rightmost rack.
Rack Configuration
2474 mm (97.4 in.)
3564 mm
(141 in.)
915 mm
(36 in.)
915 mm
(36 in.)
610 mm (24 in.)
610 mm (24 in.)
Front
Caster
Location
(4.8)121
(3.1)
80
Note: Rack units are large and heavy and are not easily moved. Because maintenance
activities require access at both the front and back, allow for extra room. The
footprint shows the radius of the swinging doors on the rack. The figure shows
the minimum space required.