alternated with single-pole breakers, so that the three-pole breakers do not all begin on Phase A.
The following figure shows another way of distributing the unbalanced load evenly. In this case, the
three-pole breakers are alternated with two-pole breakers.
Chapter 2. Physical Characteristics of Systems 165