800b0108-1301xxxx Redundancy Lost for [RedundancySetElementName] has asserted. (Power Unit)
Explanation: This message is for the use case when Redundancy Lost has asserted.
May also be shown as 800b01081301xxxx or 0x800b01081301xxxx
Severity: Error
Alert Category: Critical - Redundant Power Supply
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0802
SNMP Trap ID: 9
Automatically notify Support: No
User response:
1. Check the LEDs for both power supplies.
2. Follow the actions in Power-supply LEDs.
800b010a-1e81xxxx Redundancy Lost for [RedundancySetElementName] has asserted. (Fan Zone 1)
Explanation: This message is for the use case when Redundancy Lost has asserted.
May also be shown as 800b010a1e81xxxx or 0x800b010a1e81xxxx
Severity: Error
Alert Category: Critical - Fan Failure
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0802
SNMP Trap ID: 11
Automatically notify Support: No
User response:
1. Make sure that the connectors on fan n are not damaged.
2. Make sure that the fan n connectors on the system board are not damaged.
3. Make sure that the fans are correctly installed.
4. Reseat the fans.
5. Replace the fans. (n = fan number)
800b010a-1e82xxxx Redundancy Lost for [RedundancySetElementName] has asserted. (Fan Zone 2)
Explanation: This message is for the use case when Redundancy Lost has asserted.
May also be shown as 800b010a1e82xxxx or 0x800b010a1e82xxxx
Severity: Error
Alert Category: Critical - Fan Failure
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0802
SNMP Trap ID: 11
Automatically notify Support: No
User response:
1. Make sure that the connectors on fan n are not damaged.
2. Make sure that the fan n connectors on the system board are not damaged.
3. Make sure that the fans are correctly installed.
800b0108-1301xxxx • 800b010a-1e82xxxx
414
IBM System x3550 M4 Type 7914: Installation and Service Guide