NOTE:Thenextsectioncanonlybeselected
insoftwarerevisionsfrom443.207.000and
above.
Plant – SL2 230V External heat source
availability and control conguration
The Master boiler can control an External
heatsourcetoprovideheatintothecascade.
Inordertodothis,itrequiresaninputsignal
to inform it as to when the External heat
source is available. SL2 is used as the
input to tell the Master that the External
heatsourceisavailabletosupplyheatinto
thecascade.
Oncethisisdetermined,thecontrolsignalfor
theExternalheatsourcemustbedened.It
ispossibletoselectthe0-10Voutputorone
oftheMFRMulti-FunctionRelays,1to4.
.
Congure SL2
None
Ext. heat source release
Congure SL2
None
Ext. heat source release
OnceExt. heat sourcereleaseisselected
therequiredcontrolsignalcanbeselected
andcongured.
Ext. heat source control
None
PWM/0-10V ()
MFR1 ()
Ext. heat source control
None
PWM/0-10V ()
MFR1 ()
MFR2 ()
Ext. heat source control
PWM/0-10V ()
MFR1 ()
MFR2 ()
MFR3 ()
Ext. heat source control
MFR1 ()
MFR2 ()
MFR3 ()
MFR4 ()
Ext. heat source control
MFR2 ()
MFR3 ()
MFR4 ()
Ext. heat source control
MFR3 ()
MFR4 ()
0-10V Ext. heat source control settings.
Ifthe0-10Voutputisselectedtocontrolthe
demandtotheExternalheatsource,thenthe
followingparametersmustbeset.
ThevoltagethresholdtoturnontheExternal
heatsource.
Congure voltage demand
0.0V
Done
Congure voltage demand
1.5V
Done
Congure voltage off
0.0V
Done
Congure voltage off
1.0V
Done
External heat source capacity
Inordertobeabletodeterminethecapacity
ofthe cascade theMasterboilerneedsto
knowwhatthemaximumcapacityratingof
theExternalheatsourceis.
Maximum rating
35.0kW
Done
Maximum rating
80.0kW
Done
Thedemandswitchoncapacityfortheexternal
heatsourcecanthenbeset.
Switch on capacity
60%
Done
Switch on capacity
40%
Done
The next plant control signal that may be
conguredistheOpenThermBussignalwhich
isabidirectionalsignaltothecascade.
OpenTherm
Thisbussignalcanbothcontrolandmonitorthe
statusofthecascadeviatheMasterboiler.It
hasanumberofmodesofoperation:
1. On/Offdemand
2. Temperaturesetpointdemand
3. Capacity setpoint demand
IfnoOpenThermcontrolofthecascadeis
requiredthen‘None’maybeselected.
Congure OpenTherm
No
On demand
Temperature demand
The options that may be selected are as
below,if ‘On demand’ is selected this is
effectivelyaPELV‘voltsfree’enablesignal.
Congure OpenTherm
None
On demand
Temperature demand
Capacity demand
If ‘On demand’ is congured then this will
thenpromptforaCascadeowtemperature
setpoint,whichwillbethetargettemperature
for the cascade under direct OpenTherm
control.
OpenTherm Temp. Setpoint
60ºC
Done
OpenThermTemperaturedemand
Congure OpenTherm
On demand
Temperature demand
Capacity demand
WhenOpenThermTemperaturedemandis
selected,themaximumtemperaturethatan
OpenTherm master can demand from the
Plantcanbeadjusted.
Set max ow temp
80ºC
Done
Set max ow temp
85ºC
Done
Oncethislevelisset,‘Done’maybeselected.
Thenextplantfunctionthatmaybeselected
istheoutsidesensorinputifoneistobeused
forthecontroloftheowtemperaturefromthe
cascade.Ifnotthenselect‘Done’.
Outside sensor available?
None
Yes