72
ifm Operating Instructions IO-Link Master with EtherNet/IP interface StandardLine 8 Ports IP 65 / IP 67 (AL1122) 2017-05-31
Appendix
>
Input assembly
11134
Byte
Content
0
Digital inputs of the IO-Link ports in the DI operating mode ( Mapping: digital input data (DI) ( p. 73))
1
2
Status information ( Mapping: Status information ( p. 73))
3
4...45
Acyclic command area: Response channel ( Response channel ( p. 79))
46...63
Port X01: Diagnostic, vendor ID, device ID, events ( Mapping: IO-Link port information ( p. 74))
64...81
Port X02: Diagnostic, vendor ID, device ID, results ( Mapping: IO-Link port information ( p. 74))
82...99
Port X03: Diagnostic, vendor ID, device ID, events ( Mapping: IO-Link port information ( p. 74))
100...117
Port X04: Diagnostic, vendor ID, device ID, events ( Mapping: IO-Link port information ( p. 74))
118...135
Port X05: Diagnostic, vendor ID, device ID, events ( Mapping: IO-Link port information ( p. 74))
136...153
Port X06: Diagnostic, vendor ID, device ID, events ( Mapping: IO-Link port information ( p. 74))
154...171
Port X07: Diagnostic, vendor ID, device ID, events ( Mapping: IO-Link port information ( p. 74))
172...189
Port X08: Diagnostic, vendor ID, device ID, events ( Mapping: IO-Link port information ( p. 74))
190
Port X01: Cyclic input data (n bytes)
190+n
Port X02: Cyclic input data (n bytes)
190+2n
Port X03: Cyclic input data (n bytes)
190+3n
Port X04: Cyclic input data (n bytes)
190+4n
Port X05: Cyclic input data (n bytes)
190+5n
Port X06: Cyclic input data (n bytes)
190+6n
Port X07: Cyclic input data (n bytes)
190+7n
Port X08: Cyclic input data (n bytes)
Legend:
n = [2,4,8,16,32]; is determined by the parameter [Prozess_Data_Length] ( Process data length ( p. 69))

Table of Contents