EasyManua.ls Logo

IFM Electronic LR2750 - 11�4�7 Scale Analogue Signal; 11�4�8 Set Output Logic for the Switching Outputs; 11�4�9 Response of the Outputs in Case of a Fault; 11�4�10 Set Damping for the Measured Signal

IFM Electronic LR2750
47 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36
11.4.7 Scale analogue signal
Select [ASP2] and set the analogue start point�
Select [AEP2] and set the analogue end point�
Setting these parameters via IO-Link is only possible if parameter [ou2] =
[I] or [InEG]�
More information: (→ 6.3.2)
11.4.8 Set output logic for the switching outputs
Select [P-n] and set [PnP] or [nPn]�
11.4.9 Response of the outputs in case of a fault
Select [FOU1] / [FOU2] and set the value:
- [On] = Output switches ON in case of a fault�
Analogue output switches to a value > 21 mA in case of a fault�
- [OFF] = Switching output switches OFF in case of a fault�
Analogue output switches to a value < 3�6 mA in case of a fault�
Examples of faults: defective hardware, signal quality too low
Overflow is not considered to be a fault�
11.4.10 Set damping for the measured signal
Select [dAP] and set damping in seconds;
setting range 0,0���60,0 s (→ 6.3.4)
11.4.11 Set delay time in case of a fault
Select [dFo] and set a value between 0�0 and 10�0 s�
[dFo] only effective in case of a fault� Mind the dynamics of your application�
In case of fast level changes it is recommended to adapt the value step by
step (→ 6.3.6)
11.5 Reset all parameters to factory setting
Select [rES]
Press [Enter] until [rES] is displayed right aligned
Press and hold [▲] or [▼] until [----] is displayed.
Briefly press [Enter]�
> The unit reboots and the factory settings are restored�
Note: On delivery the unit is not operational� First, the basic settings must
be entered (→ 10.2).

Table of Contents

Related product manuals