Only if data storage is required in an IO-Link application:
The tank adjustment is not saved via IO-Link�
After a unit has failed it must be carried out again�Only when the tank
adjustment has been carried out successfully does the unit revert to the
cyclical process data transmission�
After a factory reset (button "Restore Factory Settings"), the device reboots
and the factory settings are restored�
16.2 Unit locking / data storage
The IO-Link master stores all parameters of the connected sensor (except tank
adjustment) if configured in the master (data storage)� When a sensor is replaced
by a sensor of the same type, the parameters of the old sensor are automatically
written to the new sensor if configured in the master and if the sensor allows this�
For safety reasons the parameter download can be refused by the sensor
Factory setting: [Open]
Data storage - [Open] = unit allows parameter download from the master
- [Locked] = unit refuses parameter download from the master