INSTALLER
USERMAINTENANCE TECHNICIAN
TECHNICAL DATA
Id
Parameter
Parameter Description Range Default
Customised
value
P0
Max DHW
output
Denes the maximum heat output percentage of the boiler
during the D.H.W. mode compared to the maximum heat
output available (when paired with a storage tank unit)
0 - 100 % 100 %
P1 Min CH output
Denes the minimum output percentage of the boiler in cen-
tral heating mode
0 - P2 0 %
P2 Max CH output
Denes the maximum heat output percentage of the boiler
during the central heating mode compared to the maximum
heat output available
0 - 100 %
VICTRIX
TERA V2 24
PLUS EU
G20 = 83
G31 = 83
VICTRIX
TERA V2 35
PLUS EU
G20 = 86
G31 = 86
P3 - Not available for this model - -
P4
Pump function-
ing
e pump can function in two ways.
0 intermittent: in winter “mode” the circulator is managed
by the room thermostat or by the remote control.
1 continuous: in “winter” mode the circulator is always
powered and is therefore always in operation.
0 - 1 0
P5
External probe
correction
If the reading of the external probe is not correct it is possible
to correct it in order to compensate any environmental
factors.
-9 ÷ 9 K 0
P6 - Not available for this model - -
P7 Remote control
Sets the dialogue protocol with remote device
0: IMG BUS. Select this mode when connecting an Immer-
gas remote control (e.g.: CAR v2) to terminals 44/41
1 : Not available on this model
2: Select this mode when a commercial remote control is
connected to terminals 44-41 (with this selection, the
control of the domestic hot water adjustments and max set
central heating ow remains available on the boiler panel)
0 - 2 0
P8 - Not available for this model - -