Id
Parameter
Parameter Description Range Default
Customised
value
A0
Hydraulic
model
Denes the type of hydraulics in the boiler (0 = instant; 1 =
storage tank).
0 ÷ 1 1
A1
Maximum
pump speed
Denes the maximum operating speed of the circulator (If
A1 = A2 circulator operating at set speed).
A2 - 9 9
A2
Minimum
pump speed
Denes the minimum operating speed of the circulator. 1 - A1 6
A3
Circulating
pump mode
Sets the pump operating mode
- DELTA T = 0: proportional head (see par. 1.29).
- DELTA T = 5 - 25 K: ∆T constant (see Par. 1.29).
0 ÷ 25 15
A4
Storage tank
ow oset
Establishes the temperature to be added to the DHW
set-point to calculate the ow set to heat the storage tank (if
paired with a storage tank unit)
5 ÷ 50 °C 25
A5
Storage tank
activation oset
Temperature value to be subtracted from the DHW set-point
to calculate the boiler ignition to heat the storage tank (when
paired with a storage tank unit)
0 ÷ 15 °C 3
A6 - Not available for this model - -