EasyManua.ls Logo

INVT Goodrive 35 Series - Page 284

INVT Goodrive 35 Series
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive35 inverters Communication protocol
283
Code
Name
Meaning
1. This command is only for new device;
2. Slave is in fault state and can not execute it.
02H
Illegal data
address.
Some of the operation addresses are invalid or not allowed to
access. Especially the combination of the register and the
transmitting bytes are invalid.
03H
Illegal value
When there are invalid data in the message framed received by
slave.
Note: This error code does not indicate the data value to write
exceed the range, but indicate the message frame is an illegal
frame.
04H
Operation
failed
The parameter setting in parameter writing is invalid. For example,
the function input terminal can not be set repeatedly.
05H
Password
error
The password written to the password check address is not same
as the password set by P7.00.
06H
Data frame
error
In the frame message sent by the upper monitor, the length of the
digital frame is incorrect or the counting of CRC check bit in RTU is
different from the lower monitor.
07H
Parameters
only for read
It only happen in write command
08H
Parameters
can not be
changed
during running
The modified parameter in the writing of the upper monitor can not
be modified during running.
09H
Password
protection
When the upper monitor is writing or reading and the user
password is set without password unlocking, it will report that the
system is locked.
The slave uses functional code fields and fault addresses to indicate it is a normal response
or some error occurs (named as objection response). For normal responses, the slave
shows corresponding function codes, digital address or sub-function codes as the response.
For objection responses, the slave returns a code which equals the normal code, but the first
byte is logic 1.
For example: when the master sends a message to the slave, requiring it to read a group of
address data of the inverter function codes, there will be following function codes:
0 0 0 0 0 0 1 1 (Hex 03H)
For normal responses, the slave responds the same codes, while for objection responses, it
www.barghmaher.ir

Table of Contents

Related product manuals