Goodrive35 inverters Basic operation instruction
188
Function
code
Name
Detailed instruction of parameters
Default
value
P04.23
Vibration control factor at
low frequency of motor 2
0~100
10
P04.24
Vibration control factor at
high frequency of motor 2
0~100
10
P04.25
Vibration control threshold
of motor 2
0.00Hz~P00.03 (the Max. frequency)
30.00 Hz
P04.26
Energy-saving operation
0: No action
1: Automatic energy-saving running
0
P04.27
Voltage setting
0: Keypad: the output voltage is
determined by P04.28.
1:AI1;
2:AI2;
3:AI3;
4:HDI1;
5:Multi-step speed;
6:PID;
7:MODBUS communication;
8:PROFIBUS/CANopen communication;
9:Ethernet communication;
10: Reserved
0
P04.28
Keypad setting voltage
0.0%~100.0%
(the rated voltage of motor)
100.0%
P04.29
Voltage increasing time
0.0~3600.0s
5.0s
P04.30
Voltage decreasing time
0.0~3600.0s
5.0s
P04.31
Maximum output voltage
P04.32~100.0%(the rated voltage of
motor)
100.0%
P04.32
Minimum output voltage
0.0%~P04.31(the rated voltage of motor)
0.0%
7.5 Torque control
Goodrive35 series inverters support two kinds of control mode: torque control and rotation speed
control. The core of rotation speed is that the whole control focuses on the stable speed and
ensures the setting speed is the same as the actual running speed. The Max. Load should be in
the range of the torque limit. The core of torque control is that the whole control focus on the stable
www.barghmaher.ir

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive 35 Series and is the answer not in the manual?

INVT Goodrive 35 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive 35 Series
CategoryInverter
LanguageEnglish

Related product manuals