low frequency torque. P04.01 is for the Max. Output
voltage V
b
.
P04.02 defines the percentage of closing frequency
of manual torque to f
b
.
Torque boost should be selected according to the
load. The bigger the load is, the bigger the boost is.
Too big torque boost is inappropriate because the
motor will run with over-magnetic, and the current of
the inverter will increase to raise the temperature of
the inverter and decrease the efficiency.
When the torque boost is set to 0.0%, the inverter is
automatic torque boost.
Torque boost threshold: under the threshold, the
torque boost is valid, but over the threshold, the
torque boost is invalid.
The setting range of
P04.01:0.0%:(automatic)0.1%~10.0%
The setting range of P04.02:0.0%~50.0%