Goodrive35 inverters Function codes
84
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
of the motor and its function code is P02.03; p is the
pole pair of the motor. 100.0% corresponds to the
rated slip frequencyf.
Setting range:0.0~200.0%
P04.10
Vibration
control
factor at
low
frequency
of motor 1
In SVPWM control mode, current fluctuation may
occur to the motor at some frequency, especially the
motor with big power. The motor can not run stably
or overcurrent may occur. These phenomena can be
canceled by adjusting this parameter.
The setting range of P04.10:0~100
The setting range of P04.11:0~100
The setting range of P04.12:0.00Hz~P00.03
(the Max. frequency)
10
P04.11
Vibration
control
factor at
high
frequency
of motor 1
10
P04.12
Vibration
control
threshold
of motor 1
30.00
Hz
P04.13
Motor 2
V/F curve
setting
This group of parameters defines the V/F setting
means of Goodrive35 motor 2 to meet various
requirements of different loads. See P04.00~P04.12
for the detailed function code instruction.
Note: P04 group includes two sets of V/F parameters
of the motor which cannot display simultaneously.
Only the selected V/F parameter can be shown. The
motor selection can be defined by terminals function
the shift between motor 1 and motor 2
0
P04.14
Torque
boost of
motor 2
0.0%
P04.15
Torque
boost
close of
motor 2
20.0%
P04.16
V/F
frequency
1 of motor
2
0.00
Hz