Goodrive270 series VFD for fan and pump Quick startup
-7-
2. Check whether autotuning is required. If possible, de-couple the VFD from the motor load
to start dynamic parameter autotuning. If the VFD cannot be de-coupled from the load,
perform static autotuning.
3. Adjust the ACC/DEC time according to the actual work condition of the load.
4. Perform device commissioning by means of jogging and check whether the motor rotational
direction is correct. If not, change the rotation direction by swapping any two phase wires of
the motor.
5. Set all control parameters and then perform actual run.