Goodrive270 series VFD for fan and pump Function parameter list
-215-
0: second; the running time of each step is
counted in seconds
1: minute; the running time of each step is
counted in minutes
P11 group—Protection parameters
Protection against
phase loss
0x000–0x111
Ones place:
0: Disable software input phase loss protection.
1: Enable software input phase loss protection.
Tens place:
0: Disable output phase loss protection.
1: Enable output phase loss protection.
Hundreds place: Reserved
Frequency drop at
transient power-off
0: Disable
1: Enable
If the bus voltage drops to the sudden frequency
decreasing point due to power failure, the VFD
decreases the running frequency by using the
constant bus voltage control method, which
makes the motor in power generation state. The
regenerative power can maintain the bus
voltage to ensure normal running of the VFD
until the recovery of power.
Frequency
decrease at
sudden power
failure
Note:
 This function can avoid VFD stop that is
made for the purpose of protection in grid
switchover.
 This function can be enabled only when the
input phase loss protection function is
disabled.