Goodrive270 series VFD for fan and pump Function parameter list
-161-
Function
code
Name
Description
Default
Modify
high reliability of rotation-speed tracking, but an
excessively great value may result in VFD
overcurrent.
P01.38
Demagnetization
time for speed
tracking
0.010.0s
Depends
on model
P01.39
Advanced control
for speed tracking
0x0000x111
LED ones place: Current giving mode in vector
control
0: 120% of current is given during startup, which
is switched to the given value based on P01.35
1: The current is given based on P01.35
LED ones place: PWM mode selection
0: 2PH modulation mode
1: Based on P08.40
LED hundreds place: Search direction for speed
tracking
0: Allow both forward and reverse search
1: Disallow reverse search
0x110
P01.40
KP regulation
coefficient for speed
tracking
03000
1500
P01.41
KI regulation
coefficient for speed
tracking
03000
1500
P02 group––Parameters of motor 1
Function
code
Name
Description
Default
Modify
P02.00
Type of motor 1
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
P02.01
Rated power of
AM 1
0.13000.0kW
Depends
on model
P02.02
Rated frequency of
AM 1
0.01HzP00.03(Max. output frequency)
50.00Hz
P02.03
Rated speed of
AM 1
160000rpm
Depends
on model