EasyManuals Logo
Home>INVT>Water Pump>Goodrive270 Series

INVT Goodrive270 Series User Manual

INVT Goodrive270 Series
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #262 background imageLoading...
Page #262 background image
Goodrive270 series VFD for fan and pump Function parameter list
-252-
Function
code
Name
Description
Default
Modify
P90.22
Output
characteristics
selection
0: PID output is positive.
1: PID output is negative.
0
P90.23
PID1 output gain
0.0003.000
1.000
P90.24
PID1 output filter
time
0.00060.000s
0.100s
P90.25
PID1 output upper
limit
P90.26100.0%
100.0%
P90.26
PID1 output lower
limit
-100.0%P90.25
0.0%
P90.27
Proportional gain
0.00060.000
1.000
P90.28
Integral time
0.00060.000s
5.000s
P90.29
Differential time
0.00060.000s
0.000s
P90.30
Sampling period
0.00160.000s
0.100s
P90.31
PID1 control
deadzone
0.0100.0%
0.0%
P90.32
Deadzone delay
0.0300.0s
The PID suspends the regulation when the PID
input deviation is kept for the deadzone retaining
delay time.
1.0s
P90.33
Integral separation
threshold
0.0100.0%
100.0%
P90.34
Differential filter
times
040
10
P90.35
Prior differential
processing
0: Perform differential processing on feedback
with priority
1: Perform differential processing on deviation
with priority
0
P91 group––PID2 control
Function
code
Name
Description
Default
Modify
P91.00
Unit selection
0: MPa
1: kPa
2: Pa
3: A
4: V
5: %
0

Table of Contents