Goodrive270 series VFD for fan and pump Function parameter list
-262-
P95 group––Segmented water pressure (available at use of LCD keypad)
00.00–23.59
Set the clock date and time in group P92.
Number of pressure
segments
0–8
The value 0 indicates this function is disabled.
After Tx elapsed, the water pressure changes to
that corresponding to Tx.
The water pressure before T1 is set to 0.
You need to set the end time segment.
P95.01 indicates the number of valid segments.
The setting that is out of the segment range is
invalid.
If the start time of Tx is later than the start time of
T(x+1), T(x+1) automatically changes to Tx.
P96 group––HVAC protection
Action upon water
pipe break
0: Normal running
1: Stop
Detection level of
water pipe break
After water pipe break, the VFD running
frequency boosts up to the upper limit or the PID
output upper limit frequency. When it is set to 0,
the water pipe break function is invalid.
Range: 0.0–100.0%
Detection time of
water pipe break
Used to check the detection time of water pipe
break.
Range: 0.0–6000.0s
Water pipe soft
padding function