Goodrive270 series VFD for fan and pump Function parameter list
-261-
Function
code
Name
Description
Default
Modify
3: AI2
4: AI3
5: HDIA
6: Communication card
P94.40
Water level upper
limit of inlet pool
0.0100.0%
60.0%
P94.41
Water level lower
limit of inlet pool
0.0100.0%
40.0%
P94.42
Water shortage
level of inlet pool
0.0100.0%
20.0%
P94.43
Backup pressure
upon exceptions
0.0100.0% (relative to PID1 max. value)
0.0%
P94.44
Protection value for
PID1 feedback too
low
0.0100.0% (relative to PID1 max. value)
10.0%
P94.45
Delay of PID1
feedback too low
0.03600.0s
Corresponding terminal output that is set when
PID1 feedback value is less than P94.44 and
this situation lasts the time longer than P94.45.
500.0s
P94.46
Protection value for
PID1 feedback too
high
0.0100.0% (relative to PID1 max. value)
80.0%
P94.47
Delay of PID1
feedback too high
0.03600.0s
Corresponding terminal output that is set when
PID1 feedback value is greater than P94.46 and
this situation lasts the time longer than P94.47.
500.0s
P94.48
DEC time of
emergency stop
0.0600.0s
2.0s
P94.49
ACC time with
water pump
frequency
03600.0s
Depends
on model
P94.50
DEC time with
water pump
frequency
03600.0s
Depends
on model