Goodrive270 series VFD for fan and pump Function parameter list
-260-
Function
code
Name
Description
Default
Modify
P94.29
Multi-motor
pressure loss
compensation
0: No
1: Yes
0
P94.30
Pressure reference
boost value for one
auxiliary motor
0.0100.0% (relative to PID1 reference value)
5.0%
P94.31
Pressure reference
boost value for two
auxiliary motors
0.0100.0% (relative to PID1 reference value)
10.0%
P94.32
Pressure reference
boost value for
three auxiliary
motors
0.0100.0% (relative to PID1 reference value)
15.0%
P94.33
Reserved
P94.34
Motor polling cycle
0.06000.0h
Automatic polling is targeted at idle
variable-frequency motors. The value 0
indicates no polling.
0.0h
P94.35
Running frequency
threshold for polling
P00.05P00.03
When the running frequency is greater than the
value of this function code, variable-frequency
motor polling is not performed. Otherwise, great
water pressure change impacts water supply.
45.00Hz
P94.36
Contactor closing
delay
0.2100.0s
The delay starts after the contactor closing
command is given. The VFD startup command
is given after the delay since actual contactor
closing also takes some time.
0.5s
P94.37
Contactor opening
delay
0.2100.0s
Some time is taken from giving the contactor
opening command to actual contactor opening.
After the delay, the VFD controls the motor to
switch to power frequency.
0.5s
P94.38
Manual soft startup
switching frequency
0.00P00.03
Used to check whether a motor can run properly.
50.00Hz
P94.39
Water level signal
input selection of
inlet pool
0: None
1: Digital
2: AI1
0