Goodrive270 series VFD for fan and pump    Function parameter list 
-260- 
Multi-motor 
pressure loss 
compensation 
Pressure reference 
boost value for one 
auxiliary motor 
0.0–100.0% (relative to PID1 reference value) 
Pressure reference 
boost value for two 
auxiliary motors 
0.0–100.0% (relative to PID1 reference value) 
Pressure reference 
boost value for 
three auxiliary 
motors 
0.0–100.0% (relative to PID1 reference value) 
0.0–6000.0h 
Automatic polling is targeted at idle 
variable-frequency motors. The value 0 
indicates no polling. 
Running frequency 
threshold for polling 
P00.05–P00.03 
When the running frequency is greater than the 
value of this function code, variable-frequency 
motor polling is not performed. Otherwise, great 
water pressure change impacts water supply. 
0.2–100.0s 
The delay starts after the contactor closing 
command is given. The VFD startup command 
is given after the delay since actual contactor 
closing also takes some time. 
0.2–100.0s 
Some time is taken from giving the contactor 
opening command to actual contactor opening. 
After the delay, the VFD controls the motor to 
switch to power frequency. 
Manual soft startup 
switching frequency 
0.00–P00.03 
Used to check whether a motor can run properly. 
Water level signal 
input selection of 
inlet pool 
0: None 
1: Digital 
2: AI1