frequency will drop continuously until reaching
lower limit frequency. When the output current is
detected to be lower than the current-limit level
again, it will continue accelerated running.
0x000–0x1132
Ones place:
0: Motor OL/UL pre-alarm, relative to motor
rated current.
1: VFD OL/UL pre-alarm, relative to the VFD
rated current
2: Motor output torque OL/UL pre-alarm, relative
to motor rated torque.
Tens place:
0: The VFD continues to work for an OL/UL
alarm.
1: The VFD continues to work for a UL alarm but
stops running for an OL fault.
2: The VFD continues to work for an OL alarm
but stops running for a UL fault.
3. The VFD stops running for an OL/UL alarm.
Hundreds place:
0: Detect all the time.
1: Detect during constant speed running.
Thousands place: VFD overload current
reference selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient