Goodrive270 series VFD for fan and pump Function parameter list
-217-
Function
code
Name
Description
Default
Modify
frequency will drop continuously until reaching
lower limit frequency. When the output current is
detected to be lower than the current-limit level
again, it will continue accelerated running.
Output current A
Output frequency f
Current-limit
threshold
Set
frequency
Acceleration
Constant
speed
Time t
Time t
P11.06 setting range: 50.0–180.0%
P11.07 setting range: 0.00–50.00Hz/s
P11.08
VFD/motor OL/UL
pre-alarm selection
0x000–0x1132
Ones place:
0: Motor OL/UL pre-alarm, relative to motor
rated current.
1: VFD OL/UL pre-alarm, relative to the VFD
rated current
2: Motor output torque OL/UL pre-alarm, relative
to motor rated torque.
Tens place:
0: The VFD continues to work for an OL/UL
alarm.
1: The VFD continues to work for a UL alarm but
stops running for an OL fault.
2: The VFD continues to work for an OL alarm
but stops running for a UL fault.
3. The VFD stops running for an OL/UL alarm.
Hundreds place:
0: Detect all the time.
1: Detect during constant speed running.
Thousands place: VFD overload current
reference selection
0: Related to current calibration coefficient
1: Irrelated to current calibration coefficient
0x0000
â—‹

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT Goodrive270 Series and is the answer not in the manual?

INVT Goodrive270 Series Specifications

General IconGeneral
BrandINVT
ModelGoodrive270 Series
CategoryWater Pump
LanguageEnglish

Related product manuals