Goodrive270 series VFD for fan and pump Function parameter list
-229-
Function
code
Name
Description
Default
Modify
current)
P13.04
Pull-in current
switchover
frequency
0.00HzP00.03(Max. frequency)
10.00Hz
P13.05
Reserved
P13.06
High-frequency
superposition
voltage
Used to set the pulse current threshold when the
initial magnetic pole position is detected in the
pulse mode, The value is a percentage in
relative to the rated current of the motor.
Setting range: 0.0300.0% (of the motor rated
voltage)
100.0%
P13.07
Reserved
P13.08
Control parameter 1
0x00000xFFFF
0x0000
P13.09
Control parameter 2
Used to set the frequency threshold for enabling
the counter-electromotive force phase-locked
loop in SVC 0. When the running frequency is
lower than the value of the function code, the
phase-locked loop is disabled; and when the
running frequency is higher than that, the
phase-locked loop is enabled.
Setting range: 0655.35
2.00
P13.10
Reserved
P13.11
Maladjustment
detection time
Used to adjust the responsiveness of
anti-maladjustment function. If the load inertia is
large, increase the value of this parameter
properly, however, the responsiveness may
slow down accordingly.
Setting range: 0.010.0s
0.5s
P13.12
High-frequency
compensation
coefficient of SM
Valid when the motor speed exceeds the rated
speed. If oscillation occurred to the motor, adjust
this parameter properly.
Setting range: 0.0100.0%
0.0%
P13.13
High-frequency
current-loop
0300.0%
20.0%