Goodrive35 Series Closed-loop Vector Control VFD Function parameters
106
Functio
n code
Name
Detailed instruction of parameters
Default
value
Modif
y
pre-alarm is generated, and stops after an overload
fault is reported.
2: The VFD continues to work after an overload
pre-alarm is generated, and stops after an underload
fault is reported.
3: The VFD stops after an overload/underload fault is
reported.
LED hundreds:
0: Detection all the time
1: Detection in constant-speed running
Setting range of P11.09: P11.11200%
Setting range of P11.10: 0.13600.0s
P11.11
Underload pre-alarm
detection
If the VFD current or the output current is lower than
P11.11, and its lasting time is beyond P11.12, the
VFD will output underload pre-alarm signal.
Setting range of P11.11: 0P11.09
Setting range of P11.12: 0.13600.0s
50%
P11.12
Underload pre-alarm
detection time
1.0 s
P11.13
Output terminal
action during fault
Select the action of fault output terminals on
undervoltage and fault reset.
0x000x11
LED ones:
0: Action under fault undervoltage
1: No action under fault undervoltage
LED tens:
0: Action during the automatic reset
1: No action during the automatic reset
0x00
P11.14
Speed deviation
detection
0.050.0%
Set the speed deviation detection time
10.0%
P11.15
Speed deviation
detection time
This parameter is used to see the speed deviation
detection time.
Note: Speed deviation protection will be invalid if
P11.15 is set to 0.0.
1.0 s