11. Technical references
11.5.7 System recondition (dual channel, redundancy mode inverted)
Part Description
System recondition
CH1
System recondition
CH2
Channel 1 of System recondition must have a transition of logical level 0 -> 1 -> 0.
Channel 2 of System recondition must have a transition of logical level 1 -> 0 -> 1. They
must stay at a high logical level (t) for at least 10 s and less than 30 s.
Diff Less than 100 ms. If the value is greater than 100 ms, the system maintains the outputs
deactivated.
11.5.8 System recondition (single channel)
Part Description
System recondition The channel must have a transition of logical level 0 -> 1 ->0. The time it stays at a high
logical level (t) must be at least 10 s and less than 30 s.
11.5.9 Restart signal + System recondition (dual channel, redundancy mode
coherent)
Part Description
CH1
CH2
(Restart signal)
Interchangeable channel. Both channels must have a transition of logical level 0 -> 1 -
>0. The time they stay at a high logical level (t) must be at least 200 ms and less than 5
s.
For details about the behavior of Detection signal 1 and 2 outputs and the deactivation
delay, see "Restart signal (dual channel, redundancy mode coherent)" on page125.
CH1
CH2
(System recondition)
Interchangeable channel. Both channels must have a transition of logical level 0 -> 1 -
>0. They must stay at a high logical level (t) for at least 10 s and less than 30 s.